《wincc opc通訊 simatic net配置問題》由會員上傳分享,免費在線閱讀,更多相關(guān)內(nèi)容在應用文檔-天天文庫。
1、winccOPC通訊simaticnet配置問題 診斷提示的問題如下: ================================09/21/20119:08:25AM================================ PLCDownloadtoCurrentProjectSelectedStations(288:91):Withthesetinterfaceconfiguration,communicationinSTEP7isnotpossible. PLCDownloadtoCurrentProject
2、SelectedStations(288:47):UnabletoreachthemoduleStationmanagerviatheonlineinterface. PLCDownloadtoCurrentProjectSelectedStations(13:4711):UnabletoestablishconnectiontomoduleStationmanager(Index125)instationS7200. PLCDownloadtoCurrentProjectSelectedStations(33:17074):Onl
3、ine:Driverconfigurationerrororinvalidregistryparameter. PLCDownloadtoCurrentProjectSelectedStations(13:4708):UnabletoestablishtheconnectiontothemoduleStationmanager(Index125)instationS7200. Doyouwanttocontinuedownloadingwithoutthismodule? PLCDownloadtoCurrentProjectSe
4、lectedStations(33:17074):Online:Driverconfigurationerrororinvalidregistryparameter. PLCDownloadtoCurrentProjectSelectedStations(13:4708):UnabletoestablishtheconnectiontothemoduleOPCServer(Index1)instationS7200. Doyouwanttocontinuedownloadingwithoutthismodule? 下面圖中總是顯示
5、網(wǎng)卡是STOP狀態(tài),很納悶,希望各位高手幫幫忙??! 問題補充: PLCDownloadtoCurrentProjectSelectedStations(13:4711):UnabletoestablishconnectiontomoduleStationmanager(Index125)instationS7200. 這個是什么問題?槽125是起什么作用的? 圖片說明: 1,錯誤提示1 2,錯誤提示2 3,槽號125狀態(tài) 4,stationconfigurationeditor配置
6、最佳答案 stationconfigurationeditor配置上開看組態(tài)沒有完成: 1,opcsever的狀態(tài)是“X”。 2,IEgeneral也是停止沒有連上?! 〗M態(tài)設置都正確,下載后,stationconfigurationeditor配置都沒“x” 具體的組態(tài)步驟參考: 《SIMATICNETOPCServer與S7-200/EM277的S7連接》: http://www2.ad.siemens.com.cn/download/Upload/AS/application/A03